Your default report title here...
Client(s): John Doe
Property address: 123 Main Street
Inspection date: Thursday, December 01, 2005
This report published on 12/1/2005 5:24:29 PM EST

This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited.

 


How to Read this Report
This report is organized by the property's functional areas. Within each functional area, descriptive information is listed first and shown in bold type. Items of concern follow descriptive information and are shown as follows:
Safety Poses a risk of injury or death 
Major defect Correction likely involves a significant expense 
Repair/Replace Recommend repairing or replacing 
Repair/Maintain Recommend repair and/or maintenance 
Minor defect Correction likely involves only a minor expense 
Maintain Recommend ongoing maintenance 
Evaluate Recommend evaluation by a specialist 
Concern items are sorted by the types listed above.  Click here for a glossary of building construction terms.  Contact your inspector if there are terms that you do not understand, or visit the glossary of construction terms at http://www.reporthost.com/glossary.asp
General information  
Overview: Single family detached home in well established neighborhood. 3 bedroom 1 1/2 baths
Structures inspected: home itself
Report number: 516
Time started: 1:45pm
Time finished: 3:00pm
Inspection Fee: $185.00
Present during inspection: Buyer, Owner, Realtor
Occupied: Yes
Age of building: approx. 20years
Type of building: Single family
Weather conditions: Clear
Temperature: Cool
Ground condition: Dry
Main entrance faces: East
Foundation type: Slab on grade
Exterior  
Footing material: Poured in place concrete
Foundation material: Poured in place concrete
Apparent wall structure: Concrete block
Driveway material: Poured in place concrete
Sidewalk material: Poured in place concrete
Exterior door material: Solid core steel
Water pressure (psi): 70psi
1) Extension cords are being used as permanent wiring in one or more areas. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring poses a fire and shock hazard, and is an indication that wiring is not adequate and should be updated. Recommend either removing extension cords or having a qualified, licensed electrician evaluate and make modification as necessary. For example, install additional circuits and/or electric outlets.
2) Evidence of one or more possible abandoned underground propane gas tanks was found. Left of driveway. For example, a vent pipe protruding from the soil or metal supply lines. Recommend determining if one or more underground oil tanks exist on this property. If tank(s) exists, recommend determining if it/they have been legally decommissioned.

If the tank(s) haven't been decommissioned or removed, then the clients may be liable for decommission and/or cleanup of contaminated soil in the future. Recommend the following:
  • Have the soil tested for oil contamination.
  • Have any non-decommissioned abandoned underground oil tanks legally decommissioned or removed as necessary.
  • Have contaminated soil removed as necessary
3) Recommend cleaning deck and treating with a waterproof sealant claiming to waterproof, block ultraviolet light, and stop mildew. Deck is constructed of whitewood rather than pressure treated and will not last if not treated. Consumer Reports recommends these products:

  • Cabot Decking Stain and PTW Stain
  • Olympic Water Repellent Deck Stain
  • Thompson's House and Deck Stain
  • Wolman PTW Deck Stain
  • Akzo Sikkens Cetol DEK
  • Benjamin Moore Moorwood Clear Wood Finish
  • DAP Woodlife Premium
  • Olympic Natural Look Protector Plus
 
Roof  
Roof inspection method: Traversed
Roof type: Gable
Roof covering: Asphalt or fiberglass composition shingles
Estimated age of roof: 2yrs
Roof ventilation: Adequate
4) The roof is new and in good condition except for area left of garage as shown in pictures.
5) Trees are overhanging roof and are within 10 feet of roof vertically. This is a conducive condition for wood destroying insects and organisms since organic debris is more likely to accumulate on the roof surface. Accumulated debris may cause water to enter gaps in the roof surface and leak into attic and/or interior spaces. Recommend pruning trees so they're at least 10 feet above roof, or don't overhang the roof.
 
Attached garage  
6) Extension cords are being used as permanent wiring in one or more areas. They should only be used for portable equipment on a temporary basis. Using extension cords as permanent wiring poses a fire and shock hazard, and is an indication that wiring is not adequate and should be updated. Recommend either removing extension cords or having a qualified, licensed electrician evaluate and make modification as necessary. For example, install additional circuits and/or electric outlets.
7) The garage-house door poses a fire risk because it's not fire-rated (metal or solid-core construction). Recommend having a qualified contractor replace this door with a fire-rated door.
8) The garage-house door isn't equipped with an automatic door closing device such as sprung hinges. This door should close and latch automatically to prevent vehicle fumes from entering living spaces and/or to slow the spread of fire from the garage to living spaces. A device should be installed so this door closes and latches automatically.
9) Garage door is in need of repair or adjustment. Garage door opener does not work or have receptacle to provide power.
10) The weather strip at the base of one or more garage vehicle doors is deteriorated or damaged. Recommend replacing this weather strip. As shown in picture.
11) The weather strip around one or more exterior entry doors is damaged and/or deteriorated. Recommend replacing weather stripping at entry door(s) where necessary. Front nad back doors.
 
Electric service  
Primary service type: Overhead
Primary service overload protection type: Circuit breakers
Service amperage (amps): 150
Service voltage (volts): 120-240
Location of main service panel: garage
Location of main disconnect: Breaker at top of main service panel
Service conductor material: Aluminum
Main disconnect rating (amps): 150
Branch circuit wiring type: Non-metallic sheathed
Solid strand aluminum branch circuit wiring present: Yes
shown in picture
12) This home has solid-strand branch circuit aluminum wiring. This type of aluminum wiring is a potential fire hazard. Problems due to expansion and contraction can cause overheating at connections between the wire and devices such as switches and outlets, or at splices. The Consumer Products Safety Commission recommends either discontinuing use of circuits with aluminum wiring, or pig-tailing copper wiring onto the ends of the aluminum wire. Recommend having a qualified, licensed electrician evaluate and repair or replace this wiring.

For more information, visit: http://www.inspect-ny.com/aluminum.htm
13) An insufficient number of smoke detectors are installed. Recommend installing additional smoke detectors as necessary so a functioning one exists in each hallway leading to bedrooms, and in each bedroom. For more information on smoke detectors visit http://www.cpsc.gov/cpscpub/pubs/5077.html
 
Water heater  
Estimated age: 10 yrs
Type: Tank
Energy source: Electricity
Capacity (in gallons): 40
Brand & model: mor flo
Water temperature (degrees Fahrenheit): 110
14) Temperature-pressure relief valve drain line is missing. Recommend having a qualified plumber install a drain line extending to within 6" from the floor, or routed so as to drain outside.
 
Heating and air conditioning  
Heating system energy source: Electric
Heat system type: Heat pump
A/C energy source: Electric
Air conditioning type: Split system, Heat pump
Distribution system: Flexible ducts
Filter location: In return air duct below furnace
15) Last service date of this system is more than one year ago or is unable to be determined. Recommend asking seller when it was last serviced. If unable to determine or if more than one year ago, recommend that this system be inspected, cleaned, serviced and repaired if necessary by a qualified heating and cooling technician. Recommend that this servicing be made annually in the future or as recommended by the heating and cooling contractor.
 
Attic  
Inspection method: Traversed
Roof structure type: Trusses
Ceiling structure: Trusses
Insulation material: Cellulose loose fill
Plumbing and laundry  
Location of main water shut-off valve: front of home
Location of main water meter: street
Water service: Public
Service pipe material: Galvanized steel
Supply pipe material: Galvanized steel
Vent pipe material: Cast iron
Drain pipe material: Copper
Waste pipe material: Not visible
  16) Improper wiring tapped out of washing machine outlet for lighting in rear of home.
 
Interior rooms  
17) No ground fault circuit interrupter (GFCI) devices (receptacles or circuit breakers) are visible in the kitchen or bathrooms. GFCI devices help prevent electric shocks in areas that may have water present. Recommend having a qualified, licensed electrician install GFCI protection for receptacles over counter tops and around sinks as per standard building practices. No receptacles in either bathroom.
18) Screen(s) missing in one or more windows. Window(s) may not provide ventilation during months when insects are active. Recommend installing screens.
19) One or more doors don't latch when closed. Recommend making repairs as necessary such as adjusting latch plates or lockset mechanisms.
20) One or more doors bind in their jambs. Recommend making repairs as necessary so they close easily.
21) The weather strip around one or more exterior entry doors is damaged and/or deteriorated. Recommend replacing weather stripping at entry door(s) where necessary.
22) One or more bathrooms with a shower don't have an exhaust fan installed. Even if a window that opens exists, it may not provide adequate ventilation, especially during cold weather when the window is less likely to be opened. Recommend having a qualified contractor install an exhaust fan, duct and vent cap as per standard building practices in bathrooms with showers where missing.
23) Range hood fan is inoperable. Recommend repairing as necessary. Slow to start and filter missing.
 

Photo 1  
Front of residence

Photo 2  
Roof approximately 2 yrs old.

Photo 3  
Soffit vent some need screen repair.

Photo 4  
Appears oily around service valve should be checked by professional for possible Freon leak.

Photo 5  
Soffit vent some need screen repair.

Photo 6  
Load bearing beam at front of home. Should be one continuous piece to provide full support. Although has been like this since constructed.

Photo 7  
Rear of residence.

Photo 8  
Water damage to roof sheathing under shingles from improper flashing. Noted in other picture.

Photo 9  
Water damage to roof sheathing under shingles from improper flashing. Noted in other picture.

Photo 10  
Improper flashing. Lizard shows how much space between wood and flashing. This is where water is coming in causing damage shown in prior pictures.

Photo 11  
Unfinished trim on back door.

Photo 12  
Missing weather stripping on garage door.

Photo 13  
Aluminum branch wiring present.

Photo 14  
No threshold under back door.